VELCO logo VELCO Public Outreach
Reliability Issues and Solutions 4 

3.2     Proposed Transmission Solutions, continued

Figure 35. Proposed transmission project details (the cost estimates are in year 2008 millions of dollars).

Note: the following table has been split into two parts for web viewing.

Priority number

Name

Year of Need

Load MW Needed

Low
Cost

High
Cost

Project Type

 Defi-ciencies

1

St. Johnsbury

2009

400

 $       22

 $       22

 Substation 

10

2

Middlebury

2009

700

 $       10

 $       20

 Substation 

2

3A

St Albans

2009

900

 $       25

 $       50

 Substation 

1

3B

Georgia

2009

1100

 $       20

 $       40

 Substation 

1

3C

Georgia-St. Albans

2018

1275

 $       15

 $       30

 Transmission

1

4

S Rutland

2009

1000

 $       15

 $       30

 Substation 

5

5

Blissville

2009

800

 $       15

 $       30

 Substation 

3

6

Hartford

2009

1000

 $       15

 $       30

 Substation 

4

7

Ascutney

2009

<1170

 $       14

 $       28

 Substation 

6

 8A

Newport

2009

1000

 $          1

 $          2

 Substation 

10

 8B

Queen City

2009

<1170

 $          2

 $          4

 Substation 

8

 8C

W Rutland

2009

<1170

 $          6

 $       12

 Substation 

8,  9

 8D

Ascutney

2009

<1170

 $          2

 $          4

 Substation 

6

 8E

Coolidge Reactor

2011

1200

 $          4

 $          8

 Substation 

9

9

Coolidge-Ascutney

2009

N/A

 $       25

 $       50

 Transmission

12

10

Yankee to Vernon Rd

2009

<1170

 $          5

 $       10

 Transmission

11

11

Vernon

2010

1185

 $       15

 $       30

 Substation 

14

12

Ascutney-Ascutney Tap

2013

1210

 $          5

 $       10

 Transmission

13

13

Coolidge-Cold River

2013

1210

 $       35

 $       70

 Transmission

15

14

Bennington

2009

<1170

 $       10

 $       20

 Substation 

7

15

Ascutney Transformer

2013

1210

 $          6

 $       12

 Substation 

6

16

Coolidge Transformer

2016

1245

 $       20

 $       40

 Substation 

16

17

Barre

2018

1275

 $       10

 $       20

 Substation 

19

18

Chelsea

2018

1275

 $       15

 $       30

 Substation 

4

19

Plattsburgh-Essex

2021

N/A

 $     200

 $     300

 Transmission

21, 22, 23

TOTAL

 $    512

 $    902

   

Priority number

Name

Project

Affected DUs

Lead DU

1

St. Johnsbury

Construct new ring substation at or near Lyndonville substation, install capacitor banks

CVPS, LED for station.  CVPS, LED & VEC for capacitor banks

LED

2

Middlebury

Install 2nd 115/46 kV transformer, rebuild to ring station

CVPS

CVPS

3A

St Albans

Construct new ring station with two 115/34.5 kV transformers

CVPS, VEC

CVPS

3B

Georgia

Rebuild to ring station

All Vermont Dus

CVPS

3C

Georgia-St. Albans

Construct new Georgia to St Albans 115 kV transmission line, under 10 miles.  Needed before 2018.

All Vermont Dus

VEC

4

S Rutland

Construct new substation with a 115/46 kV transformer

CVPS

CVPS

5

Blissville

Install 2nd 115/46 kV transformer, rebuild to ring station, install capacitor banks

CVPS

CVPS

6

Hartford

Install 2nd 115/46 kV transformer, rebuild to ring station

CVPS, GMP

CVPS

7

Ascutney

Rebuild to breaker-and-a-half station

All Vermont DUs, NU, NGRID

CVPS

 8A

Newport

Install capacitor banks

All Vermont DUs

VEC

 8B

Queen City

Install capacitor bank

All Vermont DUs and NGRID

GMP

 8C

W Rutland

Install capacitor banks and shunt reactors

All Vermont DUs and NGRID

CVPS

 8D

Ascutney

Add capacitor banks

All Vermont DUs, NU, NGRID

CVPS

 8E

Coolidge Reactor

Install shunt reactor

All Vermont DUs, NU, NGRID, NY

CVPS

9

Coolidge-Ascutney

Rebuild transmission line to higher rating, under 15 miles

All Vermont DUs, NU, NGRID

GMP

10

Yankee to Vernon Rd

Rebuild line for higher rating, under 10 miles

All Vermont DUs, NU, NGRID

CVPS

11

Vernon

Install 2nd 345/115 kV transformer

All Vermont DUs, NU, NGRID

CVPS

12

Ascutney-Ascutney Tap

Rebuild transmission line to higher rating, under 10 miles

All Vermont DUs, NU, NGRID

CVPS

13

Coolidge-Cold River

Rebuild transmission line to higher rating, under 20 miles

All Vermont DUs, NY

CVPS

14

Bennington

Rebuild to ring substation, install capacitor banks

All Vermont DUs,  NGRID

CVPS

15

Ascutney Transformer

Install 2nd 115/46kV transformer

CVPS, Ludlow for station

CVPS

16

Coolidge Transformer

Install 2nd 345/115 kV transformer

All Vermont DUs, NU, NGRID, NY

CVPS

17

Barre

Install 2nd 115/34.5 kV transformer and rebuild to ring station.  2018 assumes there will be an upgrade to the 34.5 kV system

GMP, WEC

GMP

18

Chelsea

Install 2nd 115/46 kV transformer, rebuild to ring station

CVPS, WEC

CVPS

19

Plattsburgh-Essex

Construct new Plattsburgh to Essex 230 kV transmission line, parallel with existing 115 kV lines, under 30 miles, NOTE: timing may be 2016 or earlier depending on other possible scenarios

All Vermont DUs

GMP

TOTAL

* R&J = Readsboro and Jacksonville

 